Chiller Data. Prior to the start of testing, record manufacturer,
type, size, and serial number of the chiller, and obtain
chiller performance data from the manufacturer. The use of
chiller performance data for Method #1 may be limited by the
chiller’s date of production and assumptions of manufacturer’s
data (see Clause 3.1 for a discussion on the use of
manufacturer’s data).
Chiller and System. Evaluate and record the physical
condition of the chiller. Record dimensions and physical
condition of the evaporator and condenser piping, location of
existing instrumentation, and locations and descriptions of
pumps or other equipment adjacent to the chiller.
Calibration. Prior to the testing, calibrate all measurement
instruments, or provide evidence of current calibration,
in accordance with Annex A2.
Instrumentation. Choose and connect measurement
instruments in accordance with clauses 6 and 7 and Annexes
A and B and all requirements of the instrumentation manufacturers.
Operation. Establish and verify prescribed operating
conditions and proper operation of chiller and test equipment
before initiating test.