2. Installation level of the electrical equipment shall be as specified in the following, unless otherwise noted.
(1) Distribution board, power switch board etc.:1800mm above finished floor to the top
(2) Motor control pushbutton switch :1500mm above finished floor to the handling group.
(3) Welding receptacle: 1200mm above finished floor to the center
3. For connection to vibrating equipment such as motors, unit heaters etc, use flexible conduit.
Or direct cable connection with using cable gland.
4. Color coding of power circuit conductors shall be as follows:
Phase R- yellow neutral- light blue
Phase S-green Ground/PE- yellow green
Phase T- red