Type and special test of similar Generator Transformer application and of similar rating"Supplier to note that all the type test certificate shall comply with requirement as mentioned in the DEP 33.65.40.31 cl no 10 and IEC 60076-1 cl no 11 and the type tests shall be performed on relevant transformer conforming to the project requirement as 15/134.5 kV, 125/165 MVA transformer.If type test are not avialable with supplier, the cost of the type test shall be included as an Optional Price.Moreover, special test if applicable shall be quoted as optional price. "