The smart meters shall be able to record 15-minute three (3) decimal points load profile data with not less than four (4) channels consisting of total import kW, total export kW, total import kvar and total export kvar demand.
For transformer (CT and VT) operated 3-phase meters, the additional channels for recording of 15-minute three (3) decimal points load profile data as specified in Table 3 shall be required.
The load profile data shall be stored in non-volatile memory. The storage capacity of the memory shall be able to store the data of each channel for not less than 45 days.